IGS-9084GP-FB2-MM-LCManaged switch, 8+4 fiber, 30 ms ring recovery, DIN-rail
IGS-9084GP-FB2-MM-LC is a managed industrial Ethernet switch with Fast/Gigabit copper ports and 4 multi-mode and single-mode fiber ports, for connecting devices in industrial settings on DIN-rail or wall mounting.
On the network side, the O-Ring, O-Chain, Open-Ring, MRP, RSTP and MSTP redundancy protocols allow a ring recovery time of 30 ms. EMC compliance covers CISPR 32, EN 55032, FCC Part 15B and the IEC 61000-4 series for ESD, RS, EFT, Surge, CS and PFMF, with EN 60950-1 electrical safety.
At a glance
- Fiber ports (SFP/FX): 4
- Fiber port speed: 100/1000Base-X
- Fiber mode: Multi-mode
- Serial interfaces: RS-232 in RJ45 connector with console cable. 115200bps, 8, N, 1
- Management: Managed
Technical specifications
| Copper ports (RJ45/M12) | 8 |
|---|---|
| Fiber ports (SFP/FX) | 4 |
| Fiber port speed | 100/1000Base-X |
| Fiber mode | Multi-mode |
| Serial interfaces | RS-232 in RJ45 connector with console cable. 115200bps, 8, N, 1 |
| Management | Managed |
|---|---|
| Copper port speed | 10/100/1000 Gigabit10/100 Fast |
| Redundancy protocols | O-ChainMRPMSTPRSTPOpen-RingO-Ring |
| Ethernet standards | IEEE 802.3, IEEE 802.3ab, IEEE 802.3ad, IEEE 802.3u, IEEE 802.3x, IEEE 802.3z |
| Forwarding mode | Store-and-forward |
| Switching bandwidth | 24 Gbps |
| Switching latency | 7 us |
| MAC table | 8192 address |
| Jumbo frame | 9.6 KB |
| Priority queues | 8 queue |
| Ring recovery time | 30 ms |
| Power input | 12–48 V |
|---|---|
| Redundant input | Yes |
| Power consumption | 13 W |
| Alarm relay | Yes(1A@24VDC) |
| Mounting | Wall MountDIN Rail Mount |
|---|---|
| Dimensions | 96.4 × 154 × 105.5 mm |
| Weight | 1.205 kg |
| Operating temperature | -40–75 °C |
|---|---|
| IP rating | IP30 |
| Storage temperature | -40–85 °C |
| Manufacturer warranty | 5 year |
| EMC (emission/immunity) | IEC 61000-4-8 PFMFCISPR 32IEC 61000-4-3 RSIEC 61000-4-2 ESDIEC 61000-4-4 EFTIEC 61000-4-5 SurgeIEC 61000-4-6 CSEN 55032FCC Part 15B |
|---|---|
| Electrical safety | EN 60950-1 |
Data extracted from the manufacturers' technical sheets: the official product spec sheet remains the reference for final confirmation.
Documentation
In the same family
More products from the same series: select up to 3 and compare them side by side.
In the same category

Let's talk about your project
Phone and email go straight to our technical sales team in Turin: the first answer is already a technical one.